Fire Risks Prompt Scrutiny of FRP Panels in Construction

October 2, 2025

Dernières nouvelles de l'entreprise Fire Risks Prompt Scrutiny of FRP Panels in Construction

Imagine a sudden fire rapidly spreading through a building, while the fire safety measures you rely on fail due to a seemingly ordinary material—fiber-reinforced plastic (FRP) panels—resulting in incalculable damage. This is not an exaggeration. FRP panels, widely used as interior building materials, often conceal overlooked fire hazards that demand urgent attention.

Understanding FRP Panels

Fiber-reinforced plastic (FRP), sometimes called glass-reinforced plastic (GRP), is a composite material consisting of a polymer matrix reinforced with fibers. The fibers are typically glass but may also include carbon, basalt, cellulose, or even asbestos. The polymer matrix is usually polyester resin, though other thermosetting plastics may be used.

In architecture, FRP panels are primarily employed as interior finishes, offering several advantages:

  • Scratch-resistant surfaces due to specialized textures
  • Easy cleaning and low maintenance requirements
  • Resistance to stains, mold, and mildew, extending service life

The Fire Performance Challenge

However, FRP panels present significant fire safety concerns when improperly designed or installed. The material can facilitate rapid flame spread across surfaces, creating cascading problems:

  • Excessive sprinkler activation: Fast-moving flames may trigger multiple sprinklers simultaneously, potentially overwhelming water supply systems and reducing overall firefighting effectiveness.
  • Flame spread outpacing sprinkler response: Fire may advance beyond the point of origin before sprinklers activate, compromising initial suppression efforts and allowing fire escalation.

Critical Factors Affecting Fire Performance

Comprehensive full-scale fire testing has identified five key factors determining FRP panel behavior in fire scenarios:

1. Backing Materials

Unbacked panels: When installed without backing on either side, heat dissipates effectively, significantly slowing flame spread. This occurs because heat dissipation lowers surface temperatures, inhibiting pyrolysis reactions that produce flammable gases.

Backed panels: Even minimal spacing (a few centimeters) between panel and backing impedes heat dissipation, elevating surface temperatures and accelerating flame spread. Backing material selection proves equally critical—non-fire-resistant backings exacerbate risks.

2. Sprinkler Systems

Effective suppression: Properly designed automatic sprinkler systems can significantly retard horizontal flame spread, reduce ceiling temperatures, and extinguish fires following heat dissipation. Sprinklers achieve this by cooling burning areas and diluting flammable gas concentrations.

Design requirements: System effectiveness depends on appropriate design parameters specific to FRP characteristics, including sprinkler type, spacing, flow rate, and water pressure.

3. Flame Retardants

Spread reduction: While flame retardants cannot render FRP panels noncombustible (they remain plastic materials), they can effectively slow flame spread and assist in fire suppression after heat dissipation. Retardants function through various mechanisms like protective layer formation, heat absorption, or inert gas release.

Performance limitations: Retardant effectiveness depends on multiple variables including chemical type, concentration, FRP formulation, and fire conditions. Therefore, they should complement rather than replace comprehensive fire protection strategies.

4. Panel Thickness

Burn-through delay: Thicker panels resist burn-through longer but paradoxically increase flame spread rates. This occurs because thicker panels contain more combustible material, releasing greater heat and flammable gases when ignited.

Design balance: Selecting panel thickness requires careful consideration of fire performance, structural requirements, and cost factors. Generally, the thinnest panels meeting structural needs should be selected.

5. Reinforcement Materials

Chopped strand mats or non-woven fabrics: When comprising less than 50% by weight, these reduce panel rigidity, potentially creating holes that accelerate flame spread by increasing oxygen-fuel contact areas.

Woven rovings: Conversely, woven rovings enhance rigidity but create continuous fiber networks that facilitate faster flame propagation.

Safety Implementation Guidelines

Based on these findings, the following measures should be implemented to minimize fire risks when using FRP panels in construction:

1. Sprinkler Systems: Essential Protection

Automatic sprinkler systems must be installed in all areas with FRP panels, regardless of flame retardant treatment. Systems should meet minimum requirements including:

  • Density: 0.20 gpm/sq.ft (8 mm/min) over most remote 2,000 sq.ft (186 m²) area
  • Hose stream allowance: 250 gpm (950 l/min)
  • K-factor: Minimum K5.6
  • Temperature rating: 165°F (74°C)

These parameters represent baseline requirements. Actual designs should incorporate more rigorous evaluations based on occupancy and structural considerations.

2. Panel Installation: Optimizing Heat Dissipation

Unbacked FRP panel installation should be prioritized. Even minimal backing spacing impedes heat dissipation. When backing is unavoidable, adhere to these specifications:

  • Maximum thickness: 1/16 inch (1.6 mm)
  • Maximum weight: 8 oz/sq.ft (2.4 kg/m²)
  • Flame retardant treatment: ASTM E-84 compliant with flame spread index ≤25
  • Reinforcement: Chopped strand or continuous non-woven fibers

3. Backing Materials: Fire Barriers

When backing is necessary, select materials with superior thermal resistance properties such as:

  • Type X gypsum board (minimum 1/2 inch/13 mm)
  • Standard or fire-retardant treated plywood (minimum 1/2 inch/13 mm)
  • Steel (minimum 26 gauge/0.5 mm)
  • Aluminum (minimum 0.032 inch/0.8 mm)

Additionally, install quick-response perimeter sprinklers along ceiling edges near walls, positioned approximately 2 feet from walls at 10-foot intervals. These sprinklers should feature:

  • Minimum K-factor: 1/2 inch (13 mm)
  • Temperature rating: 165°F (74°C)

Perimeter systems should accommodate simultaneous operation of at least 10 sprinklers with minimum 20 gpm (76 l/min) flow per sprinkler, plus 250 gpm (950 l/min) hose stream allowance. Note that perimeter systems need not be hydraulically balanced with ceiling sprinkler systems.

4. Sandwich Panel Systems: Enhanced Protection

When FRP panels form part of sandwich panel systems (e.g., with foam polystyrene, polyurethane, or polyisocyanurate cores), implement these additional measures:

  • Increase minimum sprinkler flow to 30 gpm (114 l/min)
  • Ensure hydraulic balance between perimeter and ceiling sprinkler systems

5. Professional Risk Assessment

Given the complexity of FRP-related fire risks, professional risk assessment is strongly recommended for both existing buildings and new projects. Qualified experts can evaluate potential property loss scenarios and recommend appropriate mitigation strategies.